LEV testing a fleet of 20 mobile extractors for decorators in Hull

A painting and decorating firm brought its whole fleet of on-tool dust extractors into its Hull unit for examination - twenty portable units that go out on vans every day. Testing a fleet is a different exercise from testing a fixed system, and the result was a genuine mix: most passed, several did not, and a few had to be taken out of service.

20 units
Whole fleet examined
M / H-class
Matched to the dust
Mixed
Several failed and tagged out
COSHH Regulation 9Tested to HSG258UK-wideQuantified, photographed reports
Written by Damien Granger, LEV examiner and Manager at Phoenix Cleaning Company. Reviewed for technical accuracy against COSHH and HSG258. Published 24 October 2026.

The site

A fleet that lives on vans, tested at the depot

The firm carries out painting and decorating across the region, and its operatives use on-tool dust extractors - portable units paired with sanders and other power tools to capture dust at source. Twenty of them were brought into the company's Hull unit to be examined together, off the vans for once and all in one place.

Testing a fleet is a different job from testing a fixed installation. There is no single system to measure; there are twenty individual controls, each with its own history of use and abuse, each needing to be judged on its own. Some had clearly been looked after; others had been run hard and rarely opened up. The brief was to work through every unit and produce an honest register: which were fit to go back out, which needed work, and which should not be used at all until sorted.

It is exactly the kind of equipment that slips through the net. Because the units are small, mobile and taken for granted, they are easy to leave off a testing schedule entirely - yet each one is the thing standing between an operative and a lungful of dust.

The hazard and the law

Decorating dust is not harmless, and class matters

Preparation is dusty work, and some of that dust is genuinely hazardous. Sanding filler and plaster can release respirable crystalline silica; sanding old paint can release lead, especially from pre-1992 coatings and older; and there is fine preparation dust throughout. A portable extractor used to control that dust is local exhaust ventilation, and it carries the full Regulation 9 duty under COSHH - a thorough examination and test at least every 14 months, with a record kept, for every unit.

The twist that catches people out is filtration class. Extractors are graded L, M and H: M-class (at least 99.9% efficient) for medium-hazard dust such as wood and silica-bearing materials, and H-class (at least 99.995%) for high-hazard dust such as lead paint. Use a class below what the dust demands and the unit does something worse than nothing visible - it collects the coarse dust and returns the finest, most dangerous fraction to the air the operative is breathing. A unit can be working perfectly and still be the wrong tool for the job.

Silica
From sanding filler and plaster
Lead
From old paint - H-class dust
M / H
Class must match the dust

What we tested

Every unit, one at a time

We examined all twenty units individually. For each, we measured the airflow or suction against its rated figure, opened up and assessed the filter condition, and confirmed the filtration class was appropriate for the dust that unit is actually used on - the point where a good extractor can still be the wrong one. We checked the hose and connections, looked for any airflow indicator, and recorded a clear pass or fail for the unit.

The output of a fleet examination is a register rather than a single verdict: a line for every unit, saying whether it is fit for use, what it needs if not, and whether it should be withdrawn. That register is what lets the firm manage the fleet properly rather than hoping the kit on the vans is all fine.

What we found

Most fit for use - a handful not

UnitsFindingResult
15 unitsSuction to rating, filters serviceable, class appropriatePass
3 unitsFilters blinded - suction collapsedFail
1 unitOnly L-class but used on silica-bearing dustFail
1 unitDamaged hose - loss of captureFail

Three-quarters of the fleet passed: suction to rating, filters serviceable, the right class for the work. The five that failed told the ordinary story of portable kit run hard - three with filters so blinded their suction had collapsed, one that was only L-class yet being used on silica-bearing dust (capturing the coarse and returning the fine), and one with a damaged hose leaking capture. Each failed unit was tagged out of service so it could not quietly go back on a van, and the register recorded exactly what each needed.

The remedial actions

Fix, re-class, and put a system around the fleet

  • Replace the blinded filters - fit new filters to the three units whose suction had gone, and confirm the airflow returns to rating.
  • Re-class to the dust - replace or reassign the L-class unit so anything used on silica-bearing dust is at least M-class, and H-class where lead paint is in play.
  • Repair the hose - replace the damaged hose so capture is restored on that unit.
  • Put a register and pre-use checks in place - keep a line per unit on the 14-month cycle, replace filters before they blind, and give operatives a simple way to notice a drop in suction on site.
  • Re-test the failed units - confirm each is back to rating before it returns to service.
A van full of extractors that all switch on and roar can still be a quarter failing. Without measurement, nobody knows which - which is precisely why mobile LEV needs the same register and the same 14-month clock as anything bolted to a wall.

The outcome

A fleet you can actually account for

The firm came away with a complete register of its twenty units, five of them withdrawn and specced for fixing, and - just as valuable - a routine to keep the fleet honest between tests. The examination turned a cupboard of assorted extractors into a managed set of controls with a known status each.

What this means for any trades business

Portable LEV is still LEV, and it fails in ways you cannot see or hear: a blinded filter still roars, an under-class unit still collects dust, a split hose still switches on. On a van, there is no gauge and no one measuring. The answer is unglamorous but effective - keep a register of every unit, test the fleet every 14 months, match the filter class to the worst dust each unit meets, and build a pre-use check into the day. It is how a decorating or construction firm turns "the kit's probably fine" into something it can actually prove.

Sources and further reading

The guidance behind this case study

The duties, exposure limits and control standards described here come from the Health and Safety Executive. For your own process, always work from the current HSE guidance:

About the examiner

Damien Granger is the LEV examiner and Manager at Phoenix Cleaning Company. He carries out thorough examination and testing (TExT) of local exhaust ventilation to COSHH Regulation 9 and HSG258 across the UK - covering welding fume, wood and stone dust, chemical fume cupboards, vehicle exhaust and process extraction. Phoenix Cleaning Company has provided specialist extraction, duct cleaning and LEV services since 2001.

This is an illustrative case study based on the kind of LEV examinations we carry out. It does not depict a specific named client, and measurements shown are representative. The regulations, limits and control standards described are real and current - always check the live HSE guidance for your own process.

More from the LEV series

Read next

Questions

Frequently asked questions

Do portable, on-tool dust extractors need LEV testing?

Yes. A portable or mobile extractor used to capture dust at a power tool is local exhaust ventilation, and it is subject to the same COSHH Regulation 9 duty as a fixed system - a thorough examination and test at least every 14 months, with a record kept. It is a common blind spot: because the units are small and move around, they are easy to overlook, but the law treats them as the control they are.

What dust do painters and decorators actually create?

More than people think. Sanding filler and plaster produces dust that can contain respirable crystalline silica; sanding old paintwork can release lead from pre-1992 coatings, and much older paint can be heavily leaded; and there is general fine dust from preparation throughout. Some of this is genuinely hazardous, which is why the grade of extractor - and whether it matches the dust - matters so much.

What do L, M and H-class extractors mean?

They are filtration classes. L-class is for low-hazard dust, M-class (at least 99.9% efficient) for medium-hazard dust such as wood and silica-bearing materials, and H-class (at least 99.995%) for high-hazard, carcinogenic or toxic dust such as lead paint. Using a lower class than the dust requires means the unit captures dust and then blows the finest, most harmful fraction straight back into the air.

How do you test a whole fleet of units?

Each unit is examined individually: we measure its airflow or suction against the rated figure, inspect and assess the filter condition, confirm the filtration class is right for the dust it is used on, check the hose, connections and any airflow indicator, and record a pass or fail per unit. A fleet test produces a register - which units are fit for use, which need work, and which should be taken out of service.

Why did several units fail?

The usual reasons for portable kit: filters blinded with fine dust so suction had collapsed, a couple of units being used on silica-bearing dust while only L-class, and a damaged hose. None of these is dramatic on its own, but each means a unit that looks and sounds like it is working is not actually controlling the dust - and on a van, nobody is measuring.

What should a trades firm do to keep on top of this?

Keep a register of every extractor, test the fleet on the 14-month cycle, replace filters before they blind rather than after, match the filtration class to the worst dust each unit sees, and build a simple pre-use check so operatives notice a drop in suction on site. Mobile LEV fails quietly; a register and a routine are what catch it.