LEV Testing · Bishops Cleeve
From the engineering units to the joinery and vehicle shops, Bishops Cleeve workplaces raise fume, mist and dust that the law says must be controlled - and the control proven by a thorough examination and test.
The workshops of Bishops Cleeve are where the aerospace and engineering works weld, machine and finish metal, the joinery and timber shops cut and sand, and the vehicle shops refinish. The arc and the grinder raise weld fume and metal dust, and the joinery and spray work add wood dust, oil mist and paint mist, all of which a worker should be kept from breathing.
It is local exhaust ventilation that captures the fume and dust at source - and the control has to be proven, not assumed. Under COSHH the weld-fume arms, wood-dust extraction and spray and mist extraction must be thoroughly examined and tested at least every 14 months, measured against how they are actually run.
CNC and manual machining raises oil mist and metal dust at the enclosure and bench that has to be captured at source.
Flour, powders and steam need capture at the mixing and process points, from bakeries to production kitchens.
Saws, sanders and routers throw fine wood dust that has to be drawn off at the tool and the bench.
Weld fume and grinding dust need capture at the arm and booth, wherever steel is fabricated.
Bodyshop spray booths and prep bays carry paint mist and solvent vapour that the extraction has to hold and clear.
Fume cupboards, safety cabinets and dental and salon extraction all count as LEV and all fall due on the same clock.
Typical jobs we handle, by sector and area - representative of the work we do, not named clients.
At an aerospace machine shop in Bishops Cleeve, welding, grinding and fabricating, the extraction had lost capture and the shop was hazing by mid-shift. We surveyed the system, measured capture and static pressure, and found leakage and an overloaded filter starving the hoods. We detailed the remedials and re-tested to confirm the LEV met HSG258 before labelling it.
At a joinery unit near Bishops Cleeve, running the saws, planers and sander, the capture at the hoods had fallen off and a haze hung over the benches. We took capture readings at every hood, inspected the ductwork and filters, and found a blocked filter bank throttling the system. We specified the remedial action and, once done, re-tested and certified the control to HSG258.
Condition of hoods, ducting, filters and fan - the damage, blockage and wear that quietly drops performance.
Measured capture and face velocities at the working points, plus transport velocity and static pressure through the system.
The readings assessed against how the LEV should perform to actually control the exposure - not just whether the fan turns.
Where the process warrants it, sampling to confirm the control is keeping the substance out of the breathing zone.
A thorough examination and test under COSHH is a real assessment, not a rubber stamp. It is a structured examination of the system's condition, measurement of its actual performance, and an assessment of those readings against how the system should perform to control the exposure. It follows the HSE's guidance, HSG258, and ends in a report and a label.
We test to the HSE's guidance, HSG258, and the job ends in a report and a label on the plant: what was measured, what passed, what needs putting right, and the date the next test falls due.
We inspect the system's condition - hoods, ducting, filter and fan - and identify how it is meant to control each process.
We take the readings: capture and face velocities, duct transport velocity and static pressure at the key points.
We assess the readings against the benchmark and set out clearly whether the system is controlling the exposure.
The system is labelled with the test result and next-due date, and you get the report for your COSHH file.
At least every 14 months under COSHH Regulation 9 - and sooner for certain higher-risk processes. We set the right interval for what you run and put the next-due date on the label and the report.
A thorough-examination-and-test report against HSG258, a pass/fail on each point with any remedials listed, and a dated label on the plant showing when the next test falls due.
We set out exactly what failed and why - often a single reading such as static pressure or capture velocity - so it can be put right, and we re-test to confirm the control before certifying.
Yes - the Bishops Cleeve workshops and units, and across Bishops Cleeve and the wider Gloucestershire.
No - any LEV: welding fume arms, wood and grain dust systems, spray booths, mist extraction, fume cupboards, and dental and salon extraction all fall under the same duty and the same clock.

Welding, grinding, sawing, sanding and spraying go on across Bishops Cleeve, and each throws off something a worker should not breathe - weld fume, metal and wood dust, oil mist and paint mist. The duty is to control it at source and prove the control with a measured test.
We have carried out LEV thorough examination and testing to HSG258 since 2001, across Gloucestershire and the UK. From a machine shop to a joinery, a spray booth or a lab fume cupboard, the job ends the same way: measured readings, a clear verdict, and a label whose next-due date you can rely on.
Tell us what you run and we will examine, measure, report and label it to HSG258 - across Gloucestershire.