LEV Testing · Hartlepool
From the monumental-masonry yards to the port and engineering units, Hartlepool workplaces raise fume, mist and dust that the law says must be controlled - and the control proven by a thorough examination and test.
Hartlepool keeps a working stone and monumental-masonry trade alongside its port and engineering base. Its yards around Sandgate and the town's estates take in monumental stone masonry, cutting and dressing stone that throws off silica dust, alongside fabrication and engineering units raising weld fume, oil mist and grinding dust - all things a worker should not breathe.
Local exhaust ventilation is what captures it at source, and the law does not take the control on trust. Under COSHH the extraction has to be thoroughly examined and tested at least every 14 months, measured against how it is used - not just switched on and assumed to work. Stone dust carries respirable crystalline silica, so the control here matters more than most.
CNC and manual machining raises oil mist and metal dust at the enclosure and bench that has to be captured at source.
Flour, powders and steam need capture at the mixing and process points, from bakeries to production kitchens.
Saws, sanders and routers throw fine wood dust that has to be drawn off at the tool and the bench.
Weld fume and grinding dust need capture at the arm and booth, wherever steel is fabricated.
Bodyshop spray booths and prep bays carry paint mist and solvent vapour that the extraction has to hold and clear.
Fume cupboards, safety cabinets and dental and salon extraction all count as LEV and all fall due on the same clock.
Real jobs, described by sector and area - never by a client's name.
At a monumental-masonry yard on the Sandgate estate near Hartlepool, the dust extraction over the cutting and dressing benches had lost capture and stone dust carrying silica was drifting in the shop. We measured capture at each hood, checked the ducting and the filter, and found a fan below duty and a choked filter dragging the run. We set out the remedial action, and re-tested to confirm the control before certifying.
At a port fabrication unit near Hartlepool, the weld-fume arms over the fabrication bays had lost capture and fume was reaching the welders. We measured capture and face velocities at each arm, checked the ducting and the filters, and reported what needed putting right so it held its spec on a re-test.
Condition of hoods, ducting, filters and fan - the damage, blockage and wear that quietly drops performance.
Measured capture and face velocities at the working points, plus transport velocity and static pressure through the system.
The readings assessed against how the LEV should perform to actually control the exposure - not just whether the fan turns.
Where the process warrants it, sampling to confirm the control is keeping the substance out of the breathing zone.

The point of a thorough examination and test is to prove the extraction still controls the exposure - so we measure it, we do not eyeball it. Condition, capture and face velocities, transport velocity and static pressure are checked against the design intent under HSG258, and the result is written up and labelled on the plant.
We test to the HSE's guidance, HSG258, and the job ends in a report and a label on the plant: what was measured, what passed, what needs putting right, and the date the next test falls due.
We examine the hoods, ducting, filter and fan and identify how each is meant to control its process.
We record capture and face velocities, transport velocity and static pressure at every key point.
The readings are assessed against the design intent under HSG258, with a clear verdict on control.
The plant is labelled with the result and next-due date, and you get the report for the COSHH file.
At least every 14 months under COSHH Regulation 9 - and sooner for certain higher-risk processes. We set the right interval for what you run and put the next-due date on the label and the report.
A thorough-examination-and-test report against HSG258, a pass/fail on each point with any remedials listed, and a dated label on the plant showing when the next test falls due.
We set out exactly what failed and why - often a single reading such as static pressure or capture velocity - so it can be put right, and we re-test to confirm the control before certifying.
Yes - the the Oakesway and Sandgate estates and the town's units, and across Hartlepool and the wider County Durham.
No - any LEV: welding fume arms, wood and grain dust systems, spray booths, mist extraction, fume cupboards, and dental and salon extraction all fall under the same duty and the same clock.

Hartlepool keeps its monumental-masonry yards and port fabrication shops around Sandgate and the town's estates, cutting stone and welding steel every day - and stone dust carries silica the lungs cannot clear. Every one carries a duty to control what its work throws off - and to prove it with a measured test.
We have carried out LEV thorough examination and testing to HSG258 since 2001, across County Durham and the UK. From a machine shop to a joinery, a spray booth or a lab fume cupboard, the job ends the same way: measured readings, a clear verdict, and a label whose next-due date you can rely on.
Tell us what you run and we will examine, measure, report and label it to HSG258 - across County Durham.