Phoenix Cleaning Company Call 07961 915018
LEV Testing in Moreton

LEV Testing · Moreton

LEV testing in Moreton.

The workshops of Moreton - engineering, timber and vehicle alike - raise the fume, mist and dust that COSHH says must be captured and the capture proven by a thorough examination and test.

HSG258 examinationMeasured airflow readingsReport & labelFully insured

Where fume and dust control sits in Moreton

In and around Moreton the engineering and fabrication units weld and machine, the joinery and timber shops cut and sand, and the vehicle and refinishing shops grind and spray. Welding and grinding throw off weld fume and metal dust; the joinery and refinishing work adds wood dust, oil mist and paint mist - none of it fit for a worker to breathe.

Local exhaust ventilation catches it at source, and the law will not take that on trust. COSHH requires the weld-fume arms, the wood-dust extraction and the spray and mist extraction to be thoroughly examined and tested at least every 14 months, measured in use rather than assumed to work.

The Moreton workplaces that need an LEV test

01

Precision engineering

CNC and manual machining raises oil mist and metal dust at the enclosure and bench that has to be captured at source.

02

Food and drink production

Flour, powders and steam need capture at the mixing and process points, from bakeries to production kitchens.

03

Woodworking and joinery

Saws, sanders and routers throw fine wood dust that has to be drawn off at the tool and the bench.

04

Welding and fabrication

Weld fume and grinding dust need capture at the arm and booth, wherever steel is fabricated.

05

Vehicle body and paint

Bodyshop spray booths and prep bays carry paint mist and solvent vapour that the extraction has to hold and clear.

06

Laboratory and clinical

Fume cupboards, safety cabinets and dental and salon extraction all count as LEV and all fall due on the same clock.

Typical LEV tests around Moreton

Typical jobs we handle, by sector and area - representative of the work we do, not named clients.

Engineering unit - Moreton

A weld-fume and grinding-dust test

At an engineering unit on an estate in Moreton, welding, grinding and fabricating, the arms and hoods were barely pulling and weld fume and metal dust drifted into the workspace. We measured face velocities and static pressure, checked the run, and found undersized ducting and a worn fan. We set out the remedial work and re-tested to confirm control before certifying to HSG258.

Joinery workshop - Moreton

A wood-dust extraction test

At a joinery workshop near Moreton, running the saws, planers and sander, the system was failing to catch the wood dust at source. We took capture readings at every hood, inspected the ductwork and filters, and found a blocked filter bank throttling the system. We set out what to put right, re-tested after the work, and certified the system to HSG258.

What a thorough examination and test measures in Moreton

01

Visual and structural

Condition of hoods, ducting, filters and fan - the damage, blockage and wear that quietly drops performance.

02

Quantitative performance

Measured capture and face velocities at the working points, plus transport velocity and static pressure through the system.

03

Benchmark to design

The readings assessed against how the LEV should perform to actually control the exposure - not just whether the fan turns.

04

Air sampling, where needed

Where the process warrants it, sampling to confirm the control is keeping the substance out of the breathing zone.

LEV TESTINGMoreton

Fourteen months, and whose name is on it

A thorough examination and test under COSHH is a real assessment, not a rubber stamp. It is a structured examination of the system's condition, measurement of its actual performance, and an assessment of those readings against how the system should perform to control the exposure. It follows the HSE's guidance, HSG258, and ends in a report and a label.

We test to the HSE's guidance, HSG258, and the job ends in a report and a label on the plant: what was measured, what passed, what needs putting right, and the date the next test falls due.

  • Visual and structural examination of hoods, ducting, filter and fan
  • Measured airflow, capture and face velocities at the working points
  • Static pressure and duct transport velocity readings recorded
  • Report against the benchmark, with a label and the next-due date

Examine, measure, report, label

1

Examine

We inspect the system's condition - hoods, ducting, filter and fan - and identify how it is meant to control each process.

2

Measure

We take the readings: capture and face velocities, duct transport velocity and static pressure at the key points.

3

Report

We assess the readings against the benchmark and set out clearly whether the system is controlling the exposure.

4

Label

The system is labelled with the test result and next-due date, and you get the report for your COSHH file.

Frequently asked questions

How often does LEV have to be tested?

At least every 14 months under COSHH Regulation 9 - and sooner for certain higher-risk processes. We set the right interval for what you run and put the next-due date on the label and the report.

What do we get at the end?

An HSG258 thorough-examination-and-test report, a clear pass or fail at every point with remedials listed, and a dated plant label carrying the next test date.

What if a point fails?

We set out exactly what failed and why - often a single reading such as static pressure or capture velocity - so it can be put right, and we re-test to confirm the control before certifying.

Do you cover Moreton and the wider area?

Yes - the Moreton workshops and units, and across Moreton and the wider Merseyside.

Do you only test engineering extraction?

No - any LEV: welding fume arms, wood and grain dust systems, spray booths, mist extraction, fume cupboards, and dental and salon extraction all fall under the same duty and the same clock.

LEV testing in Moreton

In and around Moreton

Moreton works its metal, timber and vehicles, welding and grinding, sawing and sanding, and refinishing - raising weld fume, metal and wood dust, oil mist and paint mist. Every one carries a duty to control what its work throws off - and to prove it with a measured test.

20+ years of experience

We have carried out LEV thorough examination and testing to HSG258 since 2001, across Merseyside and the UK. From a machine shop to a joinery, a spray booth or a lab fume cupboard, the job ends the same way: measured readings, a clear verdict, and a label whose next-due date you can rely on.

Book your Moreton LEV thorough examination

Tell us what you run and we will examine, measure, report and label it to HSG258 - across Merseyside.