LEV Testing · Newark-on-Trent
From the sugar-beet processing factory to the engineering and finishing units, Newark workplaces raise fume, mist and dust that the law says must be controlled - and the control proven by a thorough examination and test.
Newark boils the county's sugar-beet harvest, and the factory that does it washes, slices and diffuses beet, burns lime in a kiln and dries and handles the sugar. Where a factory dries and handles sugar and runs a lime kiln the dust and fume are real - the sugar dust off the drying and handling carries a dust-explosion risk, and the lime kiln gives off a fume - and the site's engineering and finishing units add weld fume, oil mist and grinding dust, all things a worker should not breathe.
Local exhaust ventilation is what captures it at source, and the law does not take the control on trust. Under COSHH the extraction has to be thoroughly examined and tested at least every 14 months, measured against how it is used - not just switched on and assumed to work.
CNC and manual machining raises oil mist and metal dust at the enclosure and bench that has to be captured at source.
Flour, powders and steam need capture at the mixing and process points, from bakeries to production kitchens.
Saws, sanders and routers throw fine wood dust that has to be drawn off at the tool and the bench.
Weld fume and grinding dust need capture at the arm and booth, wherever steel is fabricated.
Bodyshop spray booths and prep bays carry paint mist and solvent vapour that the extraction has to hold and clear.
Fume cupboards, safety cabinets and dental and salon extraction all count as LEV and all fall due on the same clock.
Real jobs, described by sector and area - never by a client's name.
At a sugar-beet processing factory near Newark, drying and handling sugar and running a lime kiln, the extraction over the sugar-drying and handling and the lime kiln had lost capture and sugar dust and lime fume were carrying across the plant. We measured capture at the dryer, the handling points and the kiln, checked the ducting and the filter, and found a fan below duty dragging the run. We set out the remedial action, and re-tested to confirm the control before certifying.
At an engineering unit on the Brunel Drive estate near Newark, the weld-fume arms and mist extraction over the machining had lost capture and the shop was hazing by mid-shift. We measured capture and face velocities at each point, checked the ducting and the filters, and reported what needed putting right so it held its spec on a re-test.
Condition of hoods, ducting, filters and fan - the damage, blockage and wear that quietly drops performance.
Measured capture and face velocities at the working points, plus transport velocity and static pressure through the system.
The readings assessed against how the LEV should perform to actually control the exposure - not just whether the fan turns.
Where the process warrants it, sampling to confirm the control is keeping the substance out of the breathing zone.
The point of a thorough examination and test is to prove the extraction still controls the exposure - so we measure it, we do not eyeball it. Condition, capture and face velocities, transport velocity and static pressure are checked against the design intent under HSG258, and the result is written up and labelled on the plant.
We test to the HSE's guidance, HSG258, and the job ends in a report and a label on the plant: what was measured, what passed, what needs putting right, and the date the next test falls due.
We examine the hoods, ducting, filter and fan and identify how each is meant to control its process.
We record capture and face velocities, transport velocity and static pressure at every key point.
The readings are assessed against the design intent under HSG258, with a clear verdict on control.
The plant is labelled with the result and next-due date, and you get the report for the COSHH file.
At least every 14 months under COSHH Regulation 9 - and sooner for certain higher-risk processes. We set the right interval for what you run and put the next-due date on the label and the report.
A thorough-examination-and-test report against HSG258, a pass/fail on each point with any remedials listed, and a dated label on the plant showing when the next test falls due.
We set out exactly what failed and why - often a single reading such as static pressure or capture velocity - so it can be put right, and we re-test to confirm the control before certifying.
Yes - the the Brunel Drive and Northern Road estates and the town's units, and across Newark-on-Trent and the wider Nottinghamshire.
No - any LEV: welding fume arms, wood and grain dust systems, spray booths, mist extraction, fume cupboards, and dental and salon extraction all fall under the same duty and the same clock.

Newark boils the sugar-beet harvest at its factory beside the Brunel Drive engineering units, drying and handling sugar, burning lime, welding and machining - raising sugar dust, lime fume, weld fume and oil mist. Every one carries a duty to control what its work throws off - and to prove it with a measured test.
We have carried out LEV thorough examination and testing to HSG258 since 2001, across Nottinghamshire and the UK. From a machine shop to a joinery, a spray booth or a lab fume cupboard, the job ends the same way: measured readings, a clear verdict, and a label whose next-due date you can rely on.
Tell us what you run and we will examine, measure, report and label it to HSG258 - across Nottinghamshire.