Home / Kitchen Extraction Cleaning / Guide
Kitchen extraction - reading the report
A TR19 report lands on your desk full of photographs and numbers, and it is easy to file it without really reading it. But the report tells a clear story if you know what to look for - the before-and-after condition, and grease readings measured against defined limits. Here is how to read it and check it says what it should.
The short answer
A TR19 pre- and post-clean report documents the system's condition before and after cleaning, through before-and-after photographs and grease-deposit readings measured in microns. To read it: compare the before and after photos to see the transformation; understand the grease readings against TR19's limits - a mean under 200 microns being the standard between cleans, and under 50 microns confirming a compliant post-clean result. A report showing grease reduced below the post-clean threshold, with clear before-and-after evidence, is one confirming a genuine, compliant clean.
The report tells a story
A TR19 pre- and post-clean report can look like an intimidating collection of photographs and figures, but it is actually telling a straightforward story: here is the system before cleaning, here it is after, and here is the measured proof that it was cleaned to standard. Once you know that structure - a before state, an after state, and the readings that verify the change - the report becomes readable rather than opaque. It is documenting the transformation of the system from its pre-clean condition to a verified clean one.
Reading it properly is worth doing, because the report is your evidence of compliance and it pays to understand what it actually says. Rather than filing it unread, knowing how to read the two things it contains - the photographs and the grease readings - lets you confirm the clean was genuine and compliant, and understand the condition of your system. The report is designed to be evidence, and evidence is more useful when you can read it. So it is worth taking the few minutes to understand the before-and-after photos and the numbers against the standard's limits.
The photographs
The photographs are the most immediately readable part. A proper TR19 report includes before-and-after photographs taken from identical positions, so you can directly compare the condition of the system at the same points before and after cleaning. Reading them is simply a matter of looking: the before photos should show the greasy, dirty condition of the system, and the after photos, from the same positions, should show those same points cleaned. The transformation from one to the other, point by point, is visual proof that the cleaning was done.
What to look for is that the before and after are genuinely from the same positions and show a real transformation - greasy before, clean after, at matching points throughout the system. Photographs from identical positions are what make the comparison meaningful; if they match up and show the system genuinely cleaned, the photographic evidence is doing its job. This visual before-and-after is often the easiest way to satisfy yourself that a real clean happened, and it is one of the two pillars of a genuine TR19 report, alongside the measurements.
The grease readings
The grease readings are the part people find harder to read, because they are numbers in microns - but they have a clear meaning against TR19's defined limits. TR19 Grease measures grease deposit in microns and sets limits: the grease should be controlled so as not to exceed a mean of 200 microns between scheduled cleans, and a single area reading 500 microns or more needs immediate attention. So a pre-clean reading tells you how grease-laden the system was, and where it stood against these thresholds - a high reading meaning heavy build-up.
The post-clean readings are the crucial ones for compliance. A compliant post-clean result should show the grease reduced well below the limits - typically under 50 microns, the level that confirms the system has been properly cleaned to standard. So reading the post-clean readings means checking they are below that threshold: if the measured grease after cleaning is under the compliant level, the report is confirming the clean met the standard. The numbers, once you know the thresholds - 200 as the between-cleans limit, 50 as the compliant post-clean level - tell you objectively whether the system was cleaned to standard.
Checking it is compliant
Putting the photographs and readings together lets you check the report confirms what it should. A compliant, genuine report has both: before-and-after photographs from identical positions showing a real transformation, and grease readings showing the system reduced below the compliant post-clean threshold. If the report has both, and they show the system genuinely cleaned to below the standard's limits, it is confirming a proper, compliant clean - which is what you need it to do as your evidence.
What to be wary of is a report missing either pillar - photographs that do not match up or show no real transformation, or an absence of grease readings against the limits. A report with no measurements has not verified the cleanliness against the standard; one with no meaningful before-and-after photos lacks the visual proof. A genuine TR19 report should let you read a clear before-and-after story confirmed by grease readings below the compliant level. Being able to read it this way is how you check that the report - and therefore the clean it documents - actually meets the standard, rather than just filing it and hoping.
The takeaway
A TR19 pre- and post-clean report tells a clear story once you know how to read it: the system before cleaning, the system after, and the measured proof of the change. The photographs, taken from identical positions, let you compare the greasy before with the cleaned after point by point. The grease readings, in microns, tell you objectively where the system stood against TR19's limits - a mean under 200 microns being the standard between cleans, and under 50 microns confirming a compliant post-clean result.
So reading the report means comparing the before-and-after photos for a genuine transformation and checking the post-clean grease readings are below the compliant threshold. A report with both - matching before-and-after photos and readings showing the grease reduced below the standard's level - is confirming a genuine, compliant clean. Taking the few minutes to read it that way, rather than filing it unread, is how you confirm your evidence actually says what it should, and understand the condition of your system into the bargain.
Questions
It documents the system's condition before and after cleaning, through before-and-after photographs taken from identical positions and grease-deposit readings measured in microns. Together they show the transformation and verify the clean against the standard's limits.
Compare the before and after photos, which should be taken from identical positions. The before photos should show the greasy condition, and the after photos, from the same points, should show them cleaned. A genuine transformation point by point is visual proof the cleaning was done.
TR19 measures grease deposit in microns. The grease should not exceed a mean of 200 microns between cleans, and a single area at 500 microns or more needs immediate attention. A pre-clean reading tells you how grease-laden the system was against these thresholds.
The grease reduced well below the limits - typically under 50 microns, the level confirming the system has been properly cleaned to standard. Checking the post-clean readings are below that threshold tells you objectively whether the clean met the standard.
Look for both pillars - before-and-after photographs from identical positions showing a real transformation, and grease readings showing the system reduced below the compliant post-clean threshold. A report with both, showing a genuine clean to below the limits, confirms a compliant clean.
A report missing either pillar - photographs that do not match up or show no real transformation, or an absence of grease readings against the limits. A report with no measurements has not verified cleanliness against the standard; one with no meaningful photos lacks the visual proof.
We provide a clear TR19 pre- and post-clean report - before-and-after photos from identical positions and grease readings against the standard's limits - that you can read and check for yourself.